Insulation Components (Insulators, Bushings, Contact Boxes)
Select by voltage level:
-
10kV system → 12kV rated components
-
24kV system → 24kV rated components
-
35kV system → 40.5kV rated components
Select creepage distance by pollution level:
-
Clean area: 10kV≥178mm, 24kV≥355mm, 35kV≥518mm
-
Medium pollution: 10kV≥240mm, 24kV≥480mm, 35kV≥700mm
-
Heavy pollution: 10kV≥300mm, 24kV≥600mm, 35kV≥875mm
Post insulators require bending strength ≥5-6kN. APG process products are void-free with PD <10pC and consistent dimensions.
Instrument Transformers (CT & VT)
Select by accuracy class:
-
Class 0.2: Precision metering, error ±0.2%
-
Class 0.5: General measurement, error ±0.5%
-
Class 5P10: Protection, composite error ≤5%
Current transformer primary current selection:
Choose 50-80% of normal load current. Standard ratios: 100/5, 200/5, 400/5, 600/5, 800/5, 1000/5, 1500/5, 2000/5, 2500/5, 3000/5A.
Voltage transformer ratios: 6000/100V, 10000/100V, 11000/100V, 22000/100V, 33000/100V, 35000/100V.
Part 3: Surge Arresters
Select by application:
-
Distribution type (HY5WS): Transformer protection, cable heads
-
Station type (HY5WZ): Switchgear, busbars, substations
-
Capacitor type (HY5WR): Capacitor bank protection
-
Neutral type (HY1.5W): Transformer neutral point
Match voltage rating:
-
6kV system → 10kV arrester
-
10kV system → 17kV arrester
-
24kV system → 30kV arrester
-
35kV system → 51kV arrester
Quick reference by cabinet type
KYN28 (12/24kV): CH3-24kV contact box + ZJ-24Q post insulator + LZZBJ9-10 CT + HY5WZ-17 arrester
KYN61 (40.5kV): CH3-40.5/660 contact box + ZJ-35Q post insulator + JDZ-35 VT + HY5WZ-51 arrester
Ring Main Unit / Compact Substation: 630A single bushing + ZJ-10Q post insulator
C-GIS: 202/235 through bushing